Advanced Search
Telect 100A Fuse Panel 009-8004-0100N
We apologize but this item is currently unavailable. Please feel free to browse our website for other available items.
Enlarge
Item Code:
TLP00980040100N
Manufacturer:
Model:
009-8004-0100N
Category:
Item Condition Description:
Please note, this unit is used and has minor scuffs and scratches, but is fully tested, completely operational and functions as intended!
Item Description

Genuine Original Telect 100A Dual-Feed 4/4 KLM/GMT -48V Fuse Panel 009-8004-0100N. Transition to higher current demands while maintaining traditional low-current distribution with this versatile 4/4 KLM/GMT fuse panel. Combination KLM/GMT fuses help you maximize space and manage power for various network elements with just one unit.

Telect Part Number:
009-8004-0100N







Features:

• 100A input rating per bus (dual feed) in one rack unit
• Large range of output amperages
• Wire-binding output connections accept either bare wire or compression lugs
• Input connections accept two-hole compression lugs
• NEBS approved







Specifications:

Inputs
Voltage & Range -48VDC, -40V to 60V
Max. input load rating 100A per side
Max. total load rating 100A per side
Max. power dissipation at full load 40W per side @ 4800W full load per side (100Ax48V)
Percentage of full load power dissipation Less than 0.5%
Max. input interrupt device 125A
Input terminal studs (with flat washers
and KEPS nuts) Two pairs of #10-32 studs on 5/8 in. centers (3/8 in. socket).
Torque nut to 20 in.-lb (2.26 N•m).
Input wire size #4 to #2 AWG (depends on input interrupt device)
Dimensions
Nominal, without brackets Width 17.25 in. (~438 mm)
Height 1.75 in. (~44 mm)
Depth 8 in. (~203 mm)
Weight
Weight, without packaging 8.7 lbs (~4 kg)
Grounding
Earth GND terminal studs (with flat-
washers and KEPS nuts) One pair of #10-24 studs on 5/8 in. centers. (3/8 in. socket).
Torque nut to 16 in.-lb. (1.81 N•m)
Ground wire size Up to 1 AWG (depends on input interrupt device)
Alarms
Alarm relay contacts 2A @ 30 VDC
0.6A @ 60 VDC
Max. alarm card power rating @42V: 59 mA (2.48W)
@48V: 64 mA (3.07W)
@56V: 69 mA (3.86W)
@60V: 73 mA (4.38W)
Alarm wire size #22 to 18 AWG
Alarm terminals Wire binding
Environmental
Operating Temperature Range -10ºC to 55ºC (14ºF to 131ºF)
KLM Outputs
Max. KLM Output Fuse (ea.) 30A
Max. KLM Output Load (ea.) - continuous 24A
Max. Total KLM Output 100A per side
KLM Output Terminal Wire binding under #8-32 panhead screw
KLM Output Wire Size #18 to #10 AWG (depends on output fuse rating)
GMT Outputs
Max. GMT Output Fuse (ea.) 10A
Max. GMT Output Load (ea.) - continuous 8A
Max. Total GMT Output 32A per side
GMT Output Terminal Wire binding under #6-32 panhead screw
GMT Output Wire Size #24 to #12 AWG (depends on output fuse rating)
Compliance
Agency Compliance NEBS approved



Please wait...
The request is currently being processed.
Please do not navigate to another page during this process.