Genuine Original Telect 100A Dual-Feed 4/4 KLM/GMT -48V Fuse Panel 009-8004-0100. The Intermediate Fuse Panels distribute and protect higher current between power board and rack-mounted equipment. These panels are available with dual 80- or dual 100-amp input. They feature 4 KTK fuses or 4 KTK and 4 GMT fuses on each side. Sides A and B are totally isolated providing battery protection and reduced risk of total power failure.Telect Part Number: 009-8004-0100Features:Dual FeedAmps per Input Feed 100-48 VoltsTotal Number of Fuses 16GMT Fuses Dual 4KTK Fuses Dual 4Fuse Rating GMT: 10 amp max. KTK: 30 amp max.Rack Mounting 19” or 23”Mounting Offset Flush or 4”Rack Space Height 1.75” (fits 2”)Color WhiteFuse Alarm and Power Fail Alarm OuputsFuse Fail Alarm LEDPower On LEDFuse Monitoring Electronic KTK fuse monitoringPower input connector accepts a 2-hole lug compression connector (4 each included). #2 AWGFuse Distribution GMT: #6-32 screws for up to #12 AWG wire KTK: #8-32 screws for up to #10 AWG wireTechnical:Fuse Fail and Power FailPower Fail Relay Power fail relay is energized during normal operation. Upon power failure, the relay will then de-energize, closing the C - NO contacts.Fuse Fail Relay Fuse fail relay in nonenergized during normal operation. Upon a fuse failure, the relay will energize closing the C -NO contacts.Electronic KTK Fuse Monitoring KTK fuse fail circuit monitors voltage out for each KTK position. Upon voltage loss, it will light a fuse fail light associated with that position and energize the fuse fail relay, closing the C - NO contacts.KTK Fuse Fail Reset Resets the fuse fail alarm associated with the power loss of a KTK position until the next fail occurs. It does not reset the GMT fuse fail.